Characteristics
|
Specifications
Model |
QA17-K
|
QA17-B
|
QA17-A
|
QA17-H
|
Type |
Monitor Module
|
Control Module
|
Output Module
|
Isolator Module
|
Purpose |
Confirmation of external signal
|
Input & Output for all systems
|
Supply higher current such as evacuation
|
Isolate from control unit when external fault
|
System Connected |
Receive activation signal from external device
|
Series with conventional detector
|
Series with QA17-B
|
Series with all system zone
|
Input Source |
Activation signal
|
Loop signal
|
24VDC/110VAC/
220VAC |
Zone short circuit
|
Output Contacts/Load |
N/A
|
1 in 2 out COM.N.O.N.C.
1.5A@30VDC |
COM.N.O.N.C.
4A@30VDC, 2.5A@250VAC |
N/A
|
EOL Resistor |
10kΩ
|
10kΩ
|
N/A
|
N/A
|
Address Coding |
Binary
|
Binary
|
N/A
|
N/A
|
Ambient Temp. |
0oC ~ +50oC
|
|||
Material |
Fire-proof plastic
|
|||
Color |
Green
|
|||
Dimensions(mm) HxWxD |
55x28x16
|
60x76x31
|
Approval |