Characteristics
- Detector has a monitoring LED that operates about every 16 seconds ( flash ) during standby status. When there is smoke, the detector will issue fire signal after 16 consecutive confirmations. (every 0.3 second) If any dust causes flashing or an intermittent signal, it will return to normal status after 32 confirmations.
- The coating of terminal contacts meets the Rohs and provides better results on corrosion and conductive.
- Each detector has added specific components that will effectively isolate interference from electromagnetic fields and lightening strike.
- All detectors use high-density steel for the contacting plate material.
Specifications
Model |
AHS-871
|
||
Type |
2-wire
|
3-wire
|
4-wire
|
Alarm Contact |
N/A
|
N/A
|
0.8A @30V DC
0.4A @125V AC |
Voltage Range |
12 ~ 30V DC
|
||
Alarm Current |
Max.30mA
|
||
Standby Current |
20 ~ 30μA (Loop response under 75μA)
|
||
Sensitivity Setting |
Comply to EN 54
|
||
Ambient Temperature |
-10oC ~ +55oC
|
||
Material |
Fire-proof plastic
|
||
Dimensions |
111mm(Dia.) x 50mm(H)
|
||
Weight |
About 170g
|
||
Color |
White
|
Effective alert area
Building Height |
Area Covered
|
Under 4M |
150 M2
|
4 ~ 20M |
75 M2
|
Approval