Characteristics
- Heat-sensing diaphragm can operate for unlimited number of times and is not affected by room temperature. The conducting parts use gold coating to avoid oxidation.
- Uses alloy air equalizer to avoid humidity and stabilize the ventilation function. Alloy itself has many micro-holes that can expel non-fire heat to avoid false alarms.
- The unit is completely sealed; its function is not affected by humidity, dust or insects.
- This detector has passed strict quality control through automatic repetitive testing and been calibrated automatically under stable temperature and humidity conditions. Thus, quality and reliability are consistent from the first detector produced to millionth.
Specifications
Model |
AHR-871
|
||
Type |
2-wire
|
3-wire
|
4-wire
|
Alarm Contact |
N/A
|
N/A
|
0.8A @30V DC
0.4A @125V AC |
Voltage Range |
12 ~ 30V DC
|
||
Alarm Current @24V DC 470Ω |
40mA
|
40mA
|
35mA
|
Alarm Temperature |
Comply to EN54, CNS
|
||
Ambient Temperature |
0℃ ~ +55℃
|
||
Material |
Fire-proof plastic
|
||
Dimensions |
111mm(Dia.) x 45mm(H)
|
||
Weight |
About 130g
|
||
Color |
White
|
Effective alert area
Construction/Height |
Under 4M
|
4M ~ 8M |
Fire-proof Building |
90 M2
|
45 M2 |
Ordinary Building |
50 M2
|
30 M2 |
Approval